Nameplate and summer capacity explained

Nameplate capacity is the rating stamped on a generator by its manufacturer; net summer capacity is what the operator says the unit can actually deliver to the grid during summer peak, after its own plant use. Across all US generators in the 2025 EIA-860 data, summer capacity comes to 93% of nameplate. The gap is small for solar, wind and hydro and large for gas turbines and geothermal.

Every plant page on this site leads with nameplate capacity and shows summer capacity next to it. Rankings always use nameplate, so that a plant is never compared on two different measures.

The ratio by technology

TechnologyUnitsNameplateNet summerSummer as share
Gas combined cycle1,857313.4 GW282.3 GW90%
Coal steam445182.2 GW168.0 GW92%
Gas combustion turbine2,237160.2 GW135.5 GW85%
Onshore wind1,565159.5 GW158.8 GW100%
Solar photovoltaic7,968152.9 GW151.9 GW99%
Nuclear96103.7 GW98.4 GW95%
Gas steam turbine54983.1 GW76.4 GW92%
Hydro3,95180.0 GW79.9 GW100%
Battery1,00343.6 GW43.3 GW99%
Oil-fired3,80130.5 GW26.3 GW86%
Pumped-storage hydro15022.2 GW23.0 GW104%
Wood and wood waste2718,011 MW7,104 MW89%
Gas engine1,8497,299 MW7,027 MW96%
Geothermal1634,049 MW2,684 MW66%
Municipal solid waste732,265 MW1,891 MW84%
Other gases671,947 MW1,773 MW91%
Other831,655 MW1,474 MW89%
Landfill gas1,2101,587 MW1,493 MW94%
Other waste biomass199659 MW577 MW88%
Other natural gas177344 MW337 MW98%
Operable units that report both values; technologies with fewer than 40 units are left out.

Why gas turbines lose the most

A combustion turbine breathes air, and hot air is thin. On a summer afternoon the same machine moves less mass through its compressor and produces less power, which is why gas combustion turbines report summer capacity at 85% of nameplate. Combined-cycle plants recover part of that loss in their steam section and sit at 90%. Coal steam units (92%) and nuclear units (95%) lose less, mostly to their own pumps, fans and cooling systems, which run on the plant’s output.

Geothermal has the lowest ratio in the table, 66%: taken together, geothermal units report only about two thirds of their rated output as available in summer. EIA-860 records the two numbers but not the reason for the gap.

Why solar, wind and hydro look identical

For solar photovoltaic, wind and most hydro units, summer capacity is reported at or very near nameplate. For solar, the nameplate in EIA-860 is the inverter (AC) rating, which is also the most the plant can push to the grid. That does not mean these plants deliver their full rating on a summer day; how much the sun, wind or river supplies is a separate question that EIA-860 does not answer.

When summer is higher than nameplate

Some units report summer capacity above nameplate. Of the units of 50 MW or more with both figures, 465 do. The survey records both numbers as the operator reports them and does not ask why one exceeds the other. During cleaning, this site set aside 40 summer values that were negative or above 1.6 times nameplate; nameplate was kept for those units.

Which number to use

Use nameplate to compare the size of equipment and to match other EIA-860 statistics. Use summer capacity when the question is how much a plant can deliver at summer peak demand. For the full definitions see how to read the data; for plant sizes in nameplate terms see how big is a US power plant.

How big the gap is overall

Added up across the country, nameplate exceeds net summer capacity by 91.0 GW. Natural gas units account for 69% of that difference, more than any other fuel. By state, the ratio is lowest in Kentucky, where summer capacity is 86% of nameplate, and highest in Washington at 98%. The difference follows each state’s mix: fleets with a large gas share sit low, fleets of hydro, wind and solar sit near 100%.

Large plants with the widest gap

Among plants of 500 MW or more that report summer capacity for every unit, these have the lowest summer share. Their plant pages show both figures for each unit, so the units that pull the ratio down are easy to spot.

PlantStateMain fuelNameplateNet summerSummer share
Geysers Unit 5-20CaliforniaGeothermal1,236 MW644 MW52%
Goose Creek Energy CenterIllinoisNatural gas684 MW432 MW63%
Gleason Generating FacilityTennesseeNatural gas568 MW360 MW63%
Montana Power StationTexasNatural gas527 MW352 MW67%
KingstonTennesseeCoal1,700 MW1,147 MW67%
Lincoln CombustionNorth CarolinaNatural gas2,156 MW1,485 MW69%
Sonoran Solar EnergyArizonaSolar750 MW520 MW69%
White BluffArkansasCoal1,800 MW1,253 MW70%
Plants of 500 MW or more, ranked by net summer capacity as a share of nameplate.

Storage and missing values

Storage plants follow the same rule as generators: the summer figure is what they can discharge to the grid. Pumped-storage hydro units report 104% of nameplate in summer taken together, and battery units 99%. Neither number says how long the plant can keep discharging; EIA-860 records that separately for batteries, and this site does not use it.

Not every unit reports a summer figure. Of the 27,866 operable units in the data, 112 have no usable summer value, either because none was reported or because it failed the cleaning rule above. When any unit of a plant lacks the figure, the plant page shows nameplate only and leaves the summer total out instead of adding up an incomplete number. The notes on the data list every cleaning rule with the number of records it touched.

Source: U.S. Energy Information Administration, Form EIA-860 (Annual Electric Generator Report), 2025 final data (Sep 2026). Downloaded 2026-10-28. Figures are computed by GridPlants from the plant, generator and ownership files; see how to read the data.